Reduced pressure assemblies, double checks, pressure vacuum breakers and spill-resistant vacuum breakers are each tested differently. We identify yours, run its procedure, and explain the results if you'd like. The price depends on size, not type.
Pricing
| Backflow size | Flat fee per backflow |
|---|---|
| Under 4" | $105 |
| 4" and larger | $175 |
Includes the test and filing with your water district. No hidden fees.
- Price$105 flat
- TimeUnder an hour
- SchedulingSame week
- FilingIncluded
Questions before you book? Call us. We're happy to explain.
Types we work on
- RP assemblies on commercial and high-hazard lines
- PVBs and SVBs on irrigation
- Double checks on fire lines and lower-hazard services
- Detector assemblies on fire sprinkler services
Testing reduced pressure (RP) assemblies
RP assemblies, sometimes written RPZ, protect connections where the risk is highest: chemical feeds, medical equipment, boilers, car washes and similar uses. Inside are two check valves and a relief valve in the middle that opens to the air if pressure between the checks gets too close to the supply pressure.
When we test an RP, we measure when that relief valve opens and whether each check valve holds. Those readings go on the report your district reviews.
A dripping or spitting relief valve between tests usually means debris or wear on the first check. We note it on the visit and explain whether it needs attention now. Catching it early tends to be cheaper than waiting for a failed test or a valve that won't stop discharging.
Testing double check valve assemblies
A double check valve assembly has two independent check valves in a row and no relief valve. It's approved for lower-hazard connections, like many fire sprinkler systems and some irrigation and domestic lines.
The test confirms that each check valve holds pressure in the direction it's supposed to. The tester isolates each check in turn using the shutoff valves and test cocks, then reads the gauge.
Double checks are often installed below ground in vaults or boxes, especially on fire lines. That can make access the hardest part of the job. If your device sits in a vault that fills with water or dirt, let us know when you book so we come ready to pump it out before the test.
Vacuum breakers on irrigation lines
PVBs and SVBs are common on residential and commercial irrigation. They're the above-ground devices with a bonnet on top, usually near the sprinkler valves. Their job is to stop water from being siphoned back out of the sprinkler lines when pressure drops on the supply side.
The test checks two things: that the air inlet opens and that the check valve holds tight. It's quick, and these are often the easiest devices to reach.
Placement matters with these. They need to be above the highest downstream sprinkler or outlet to work as designed. If yours looks too low, we'll tell you, because a device can pass its readings and still be installed wrong.
Testing devices on fire sprinkler services
Many commercial and multi-unit buildings have a double check detector assembly (DCDA) or a reduced pressure detector assembly (RPDA) on the fire sprinkler line. These have a small bypass with a meter that shows if water is being used on the fire line when it shouldn't be.
We test the main assembly and the bypass assembly, since both protect the water supply. Fire line devices are often 4 inches or larger, which falls in the $175 per device price tier.
Fire systems usually involve more than one party: the building owner, the fire sprinkler contractor and sometimes the fire department. Closing valves on a fire line can trigger alarms, so we coordinate with you first and follow the steps needed to keep the system covered.
Figuring out which type you have
Most devices have the manufacturer's name and model cast into the body or printed on a tag. The model number usually tells you the type. If you can't read it, shape helps: an RP has a relief valve port on the bottom between two checks, a double check has two check covers and no relief port, and a PVB or SVB has a bonnet on top with a single check.
You don't need to know before you book. A photo is enough for us to tell, and the tester confirms it on site before starting.
Older devices and test results
Device type matters less than condition when it comes to passing. A ten-year-old double check that has been rebuilt on schedule can pass easily, while a three-year-old RP on a line full of debris can fail.
That said, older devices do fail more often as rubber ages and parts wear. If yours is old enough that parts are getting hard to find, we'll mention it, so replacement can be planned instead of rushed.
Don't know which one you have?
A quick photo is usually enough for us to tell. Or read our comparison guide.
Questions
Is the price different for an RP?
No. We charge by size: $105 under 4 inches, $175 for 4 inches and larger.
Can you test a device installed underground?
Yes. Let us know when you book if the vault fills with water or dirt so we come ready to clear it.
Which type is most common on homes?
On sprinkler lines it's usually a PVB or double check. On the main line it's often a double check or RP.
Do fire line devices need the fire department?
Usually not for the test itself, but we coordinate with you first since closing valves can trigger alarms.
Is an RPZ the same as an RP?
Yes. Both names refer to a reduced pressure principle assembly.
Do all types cost the same to test?
Pricing goes by size, not type: $105 for devices under 4 inches and $175 for 4 inches and up.
Why Pasadena customers choose us
We focus on backflow prevention, so we know the devices, the test procedures and what your water district expects to see. Our testers are certified, our gauges are kept in calibration, and we'll explain what we find in plain terms.
You'll always know the price before work begins. Testing is $105 per device under 4 inches and $175 for 4 inches and larger, and other work is quoted free. Our office answers seven days a week, 6am to midnight, and emergency calls are answered 24/7.
Many of the people who call us have never dealt with a backflow device before, and that's fine. We'll tell you where the device is, what the test involves, and what the readings mean, without the jargon. If a repair or replacement comes up, you'll get the reasons and the price in writing so you can decide on your own schedule. Nothing gets done without your okay.
Serving Pasadena and nearby cities
We provide backflow preventer testing throughout Pasadena and nearby, including South Pasadena, San Marino, Altadena, East Pasadena and Highland Park. Most appointments are available within the week.